Posts

Showing posts from May, 2022

KVAR RATING CALCULATOR,CAPACITOR BANK SIZE CALCULATION

Image
  Determination of Required Capacitor Rating by measurement 3 Methods are used. 1. Measurement with current and power factor 2.Measurement with recording of Active and Reactive power. 3.Measurement by Reading Meters . 1 . Measurement with Current and power factor The active power P is calculate from the measured voltage V ,apparent current Is and Power Factor P=√3*Voltage*apparent Current*cosψ *10^-3 If the desired power factor cosψ has been specified, the capacitor power rating can be calculate from the following formula: Qc = P. (tan ψactual - tanψ desired) Let's See the Example Measured Apparent Current Is : 248 Amps Power Factor cos ψ1 = 0.86 Desired Cos ψ2 = 0.92 Voltage V :397 V p=√3 * 397 * 248 * 0.86 * 103 P = 146.6 KW Qc= P. (tanψ actual - tanψ desired) = 146.6(0.59 - 0.42) = 24.9 KVAR

Estimation of Uncertainty in Hardness Measurement & Maximum Permissible Error of Brinell Hardness Testing Machine As Per ISO 6506-2 & ASTM E10-15

Image
Source of Uncertainty of Hardness Measurement Certified Value of CRM Determine the User Machine Repeatability Assessment according EN ISO 6506 Uncertainty from the Measured Material. Resolution of the Indentation diameter measuring device.                            1. Certified Value of CRM       Xcrm = 222 HBW 10/3000    Ucrm    = 土 1.4 HBW  (2σ Uncertainty) 2 . Determine the User Machine Repeatability       H₁ = 221     H₂ = 220      H₃ = 220      H₄ = 221      H₅ = 220     Mean = 220  HBW                      b )  Repeatability of  Hardness Measurement                      H₅ = 220              ...