KVAR RATING CALCULATOR,CAPACITOR BANK SIZE CALCULATION

Image
  Determination of Required Capacitor Rating by measurement 3 Methods are used. 1. Measurement with current and power factor 2.Measurement with recording of Active and Reactive power. 3.Measurement by Reading Meters . 1 . Measurement with Current and power factor The active power P is calculate from the measured voltage V ,apparent current Is and Power Factor P=√3*Voltage*apparent Current*cosψ *10^-3 If the desired power factor cosψ has been specified, the capacitor power rating can be calculate from the following formula: Qc = P. (tan ψactual - tanψ desired) Let's See the Example Measured Apparent Current Is : 248 Amps Power Factor cos ψ1 = 0.86 Desired Cos ψ2 = 0.92 Voltage V :397 V p=√3 * 397 * 248 * 0.86 * 103 P = 146.6 KW Qc= P. (tanψ actual - tanψ desired) = 146.6(0.59 - 0.42) = 24.9 KVAR

LS-1008 LEAD SETTING STANDARD NOMINAL VALUE AND ACCURACY OR TOLERANCE AS PER API

All the values are inch   GROOVE DISTANCE #1 - #2 Nominal Value        0.503900 REMAINING GROOVES Nominal Value  +1.007800 +2.015600 +3.023300 +4.031100 ACCURACY OR TOLERANCE The Accuracy or tolerance of the groove distance between 1 and 2 are given below. Groove distance #1 - #2     +0.000100"/-0.000100 The Accuracy or tolerance of the remaining groove are given below +0.000200/-0.000200