KVAR RATING CALCULATOR,CAPACITOR BANK SIZE CALCULATION

Image
  Determination of Required Capacitor Rating by measurement 3 Methods are used. 1. Measurement with current and power factor 2.Measurement with recording of Active and Reactive power. 3.Measurement by Reading Meters . 1 . Measurement with Current and power factor The active power P is calculate from the measured voltage V ,apparent current Is and Power Factor P=√3*Voltage*apparent Current*cosψ *10^-3 If the desired power factor cosψ has been specified, the capacitor power rating can be calculate from the following formula: Qc = P. (tan ψactual - tanψ desired) Let's See the Example Measured Apparent Current Is : 248 Amps Power Factor cos ψ1 = 0.86 Desired Cos ψ2 = 0.92 Voltage V :397 V p=√3 * 397 * 248 * 0.86 * 103 P = 146.6 KW Qc= P. (tanψ actual - tanψ desired) = 146.6(0.59 - 0.42) = 24.9 KVAR

UNCERTAINTY OF MEASUREMENT OF ANALOGUE PRESSURE GAUGE

Image
  SOURCE OF UNCERTAINTY OF PRESSURE GAUGE Repeatability of the unit under test. Resolution of UUT Expanded Uncertainty of Master Instrument Hysteresis Error Drift of the Master Instrument\ Uncorrected Error of Master Instrument   Calibration Result    1.0  Repeatability of the instrument (U 1 ) Uncertainty from the repeatability  = 0.05774 bar 2.0  Resolution of UUT (U 2 )           Resolution of UUT  = 1 bar      Uncertainty from the resolution of the UUT =              = (1/5)/sqrt (3)                                           =0.1154700 bar                                 3.0  Uncertainty of Master Instrument (U 3 ) Expanded Uncertainty of Master Instrument  = ...